CASE  STUDY OF MREPL MIST TYPE CONDENSER INSTALLED
AT M/S SOTHERN PETROCHEMICAL INDUSTRIES CORPORATION, (SPIC),
TUTICORIN FOR THEIR UREA CONCENTRATOR.

In SPIC Urea Plant, direct contact Barometric Condensers are installed for condensing the vapour and steam jet ejector for creating vacuum.

Around 45 TPH of vapour  is condensed in these condensers  and 700 mm Hg  of vacuum is created by Ejectors.

The above was carried out by using a Primary & a Secondary Condenser.  The uncondensed vapours  from primary condenser  were taken to secondary condenser.  Vapour quantity entering secondary condenser including inerts is around 1 TPH.  The uncondensed vapours from secondary condenser were vented to atmosphere through another ejector.

For this operation they were using total 2200 M3/hr of water &  1 TPH steam at 20 kg/cm2 pressure.

To save the above steam, SPIC  decided to convert the existing system to MREPL Mist type condensing system in 2 stages.  In the 1st  stage, a baby MTAT condenser was installed at the  outlet of 1st jet ejector where 90 M³/Hr water  was  entering at a pressure of 1 kg /cm2 and a temperature of 35°C.

MTAT condenser  is now condensing  the vapour as well as producing 700 mmHg  vacuum.  The steam pressure reduced from operating 15 kg /cm2 to 10 kg/cm2 thus saving steam required for the secondary jet ejector.

Now, in the Second stage we shall replace the primary ejector with MTAT Condenser to totally nullify the consumption of steam by isolating the existing steam jet ejectors. The system shall be commissioned  shortly.