Extracts from the text of Performance Certificates issued by some of our clients regarding our systems :

Gula Padang Terap Berhad (May 13, 1985) back
"The above system purchased from you, has been installed and successfully commissioned, on 5th December, 1984.

The testing for the efficiency of MCS was carried out in two stages and the results are as follows: State 1 (5.12.84 to 7.12.84) (WET BULB 30 °C). Process systems were operated to obtain highest vacuum in vacuum pans.

Injection pumps operated 6500 M3/hr. : 10 units (100%)
MCS spray pumps operated 5500 M3/hr. : 3 units (100%)
Water temps during Ambient : 36 °C
Highest ambient Hot water : 37 °C
Temps. Cold Water : 28 °C
Average temps per day Ambient : 32.5 °C
Hot water : 34.5 °C Cold water : 27.5 °C

It was found that the cold water temperature was steady at 27.5 °C-29 °C even though the hot water temperature ranged from 32 °C-37 °C. continued ...